Trane Furnace Clearance to combustibles
Trane Furnace Clearance to combustibles: reference table for the furnace (Trane S8V2 series): a quick-reference table with notes.
Trane Furnace Clearance to combustibles table
| Cabinet width | Vertical sides / top | Horizontal sides / top |
|---|---|---|
| 14.5 in. | 0 / 1 in. | 1 / 2 in. |
| 17.5 in. | 0 / 1 in. | 1 / 2 in. |
| 21.0 in. | 0 / 1 in. | 1 / 3 in. |
| 24.5 in. | 0 / 1 in. | 1 / 5 in. |
How to use the Trane Furnace Clearance to combustibles table
Find your exact model in the first column and read across the row. Values in the Trane Furnace Clearance to combustibles table are a summary for quick reference; the rating plate on the unit and the manufacturer's manual for your model always decide. If your model is not listed, or a value looks different from what you see on the unit, check the manual before changing anything.
Notes
- 24 in. front service access.
- 3 in. in front of the combustion air openings.
- Downflow on combustible floor without coil needs BAYBASE205.
- Garage: burners and igniter at least 18 in. above floor.
Applies to: All S8V2 models
Trane models this applies to
S8V2A040M3PCBS8V2A040M3PDS8V2B060M4PCBS8V2B060M4PDS8V2B080M4PCBS8V2B080M4PDS8V2C080M5PCBS8V2C080M5PDS8V2C100M5PCBS8V2C100M5PDS8V2D120M5PCBS8V2D120M5PD
Source: Trane FNR-SVX003A-EN (S8V2) - Table 5. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.