Icon
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Rheem Furnace Clearance to combustibles (all models)

Updated · by Aurora Star Tech Inc.

Rheem Furnace Clearance to combustibles (all models): reference table for the furnace (R95P series): a quick-reference table with notes.

FurnaceClearancesR95P

Rheem Furnace Clearance to combustibles (all models) table

LocationMinimum clearance
Left side0 in.
Right side0 in.
Back0 in.
Top1 in.
Front2 in.
Vent0 in.
Service (front)24 in. recommended

How to use the Rheem Furnace Clearance to combustibles (all models) table

Find your exact model in the first column and read across the row. Values in the Rheem Furnace Clearance to combustibles (all models) table are a summary for quick reference; the rating plate on the unit and the manufacturer's manual for your model always decide. If your model is not listed, or a value looks different from what you see on the unit, check the manual before changing anything.

Notes

  • Same values for R95PA040 through 115.
  • Column order read from a rotated drawing header - confirm on the furnace clearance label.
  • Downflow non-zero-clearance installs need the right-side vent clearance in Figure 4, otherwise use kit RXGY-ZK.

Applies to: R95PA040, 060, 070 (1317MSA), R95PA085, 100 (1521MSA), R95PA115 (1524MSA); (-)95P series

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Rheem models this applies to

R95PA0401317MSAR95PA0601317MSAR95PA0701317MSAR95PA0851521MSAR95PA1001521MSAR95PA1151524MSA

Rheem Furnace error codes →

Source: Rheem (-)95P Series single-stage condensing furnace Installation Instructions 92-24161-111-03, Figure 6 Unit Dimensions (Clearance to Combustibles), p.14-15. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Furnace Repair

647-657-2977