Goodman Furnace Minimum recommended filter size

Updated · by Aurora Star Tech Inc.

Goodman Furnace Minimum recommended filter size: reference table for the furnace (Goodman/Amana GM9C96/AM9C96 series): a quick-reference table with notes.

FurnaceFiltersGoodman/Amana GM9C96/AM9C96

Goodman Furnace Minimum recommended filter size table

ConfigurationSize codeMinimum filter
Upflow*0403A*1 - 16 x 25 side or 1 - 14 x 24 bottom return
Upflow*0603A*1 - 16 x 25 side or 14 x 24 bottom return
Upflow*0603B*1 - 16 x 25 side or bottom return
Upflow*0803B*1 - 16 x 25 side or bottom return
Upflow*0804B*1 - 16 x 25 side or bottom return
Upflow*0804C*1 - 16 x 25 side or bottom return
Upflow*0805C*1 - 16 x 25 side or bottom return (see note 1)
Upflow*0805D*2 - 16 x 25 side or 1 - 20 x 25 bottom return (see note 1)
Upflow*1004C*2 - 16 x 25 side or 1 - 20 x 25 bottom return
Upflow*1005C*2 - 16 x 25 side or 1 - 20 x 25 bottom return
Upflow*1205D*2 - 16 x 25 side or 1 - 24 x 24 bottom return
Downflow*0403A*2 - 10 x 20 or 1 - 14 x 25 top return
Downflow*0603A*2 - 10 x 20 or 1 - 14 x 25 top return
Downflow*0804B*2 - 14 x 20 or 1 - 16 x 25 top return
Downflow*1005C*2 - 14 x 20 or 1 - 20 x 25 top return

How to use the Goodman Furnace Minimum recommended filter size table

Find your exact model in the first column and read across the row. Values in the Goodman Furnace Minimum recommended filter size table are a summary for quick reference; the rating plate on the unit and the manufacturer's manual for your model always decide. If your model is not listed, or a value looks different from what you see on the unit, check the manual before changing anything.

Notes

  • Note 1: with a cooling unit over 4 tons use 2 - 16 x 25 filters on two side returns or a 20 x 25 on the bottom return.
  • Upflow at 1800 CFM or more: use two side returns or one side plus bottom.
  • Larger filters are fine; filters may also be in a central return.
  • Horizontal installs: filters must be outside the furnace (central return).
  • Filters are not supplied with the furnace; replace every two months or as needed.

Applies to: Goodman/Amana GM9C96, GC9C96, AM9C96, AC9C96 two-stage 96% furnaces

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Goodman models this applies to

AC9C96AM9C96AM9C960303ANGC9C96GM9C96GM9C960303AN

Goodman Furnace error codes →

Source: Goodman RS6612020r1 (GM9C96 service), Minimum Recommended Filter Size p.16-17. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.