Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Viessmann boiler: Storage tank (cylinder) heating

Updated · by Aurora Star Tech Inc.

If your Viessmann Vitodens 200-W boiler heats an indirect hot water tank, this page explains how the boiler decides when to reheat the tank, when to stop and how it protects your radiators from being starved of heat.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

How the Viessmann boiler works: Storage tank (cylinder) heating

What this is. If your Viessmann Vitodens 200-W boiler heats an indirect hot water tank, this page explains how the boiler decides when to reheat the tank, when to stop and how it protects your radiators from being starved of heat.

What happens, in order. When the tank temperature drops below your target by the start point, tank heating begins. The standard start point is 5 °F below the target. A setting decides whether the heating circuit pump and mixing valve are held off during tank heating, which gives hot water priority. The boiler keeps heating until the tank reaches 5 °F above the target. If it runs longer than the maximum heating time, which defaults to 60 minutes, it stops even if the target is not reached. The boiler then waits at least the minimum delay, also 60 minutes by default, before heating the tank again, even if someone asks for hot water. When heating ends, the circulation pump runs on for a time, 120 seconds by default.

What is normal. The boiler heating the tank a few degrees past the target, radiators cooling briefly while the tank is reheated, and the pump continuing to run for two minutes after the burner stops.

Safe checks. Check the temperature set on the tank, make sure nobody has changed the boiler settings, and look at the pressure gauge. Do not touch the tank's valves or piping.

When to call a technician. If the water is lukewarm for hours, heating stops while the tank warms, or you see leaks, call Aurora Star Tech, who service Viessmann boilers in the GTA.

Key times at a glance

WhatHow long or how much
Start point (1085.0)default 2.5 K (5 F) below target, adjustable 1.0-10.0 K
Stop point2.5 K (5 F) above target
Max DHW heating time (1087.0)default 60 min, adjustable 1-240 min
Delay before next DHW heating (1087.1)default 60 min, adjustable 60-240 min
Circulation pump run-on (534.0)default 120 s, 0-900 s, do not set below 120 s

Applies to: Vitodens 200-W B2HE 85, 120, 150, 199

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Questions about the Viessmann boiler

What is the Storage tank (cylinder) heating on a Viessmann boiler?

If your Viessmann Vitodens 200-W boiler heats an indirect hot water tank, this page explains how the boiler decides when to reheat the tank, when to stop and how it protects your radiators from being starved of heat.

Is it normal for my Viessmann boiler to do this?

The boiler heating the tank a few degrees past the target, radiators cooling briefly while the tank is reheated, and the pump continuing to run for two minutes after the burner stops.

Who can service my Viessmann boiler near me?

Aurora Star Tech Inc. repairs and services Viessmann boilers in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977