Trane furnace: First-stage gas heating
Trane S8B1, S8X1 and S8X2 are 80 percent efficient gas furnaces. This page follows the first stage of heating, step by step, so each click and hum makes sense.
How the Trane furnace works: First-stage gas heating
What this is. Trane S8B1, S8X1 and S8X2 are 80 percent efficient gas furnaces. This page follows the first stage of heating, step by step, so each click and hum makes sense.
What happens, in order. When the thermostat asks for heat, the furnace display shows Xt (or Xt1 on the two-stage S8X2). The control first checks that its safety switches are closed and that the pressure switch is still open. The inducer, a small fan that pulls air through the furnace, then starts; on the S8X2 it begins on high for about 6 seconds before settling to low. The pressure switch must close to prove air is moving, and the furnace allows 60 seconds for that. If it does not, the display shows e3.1 and the inducer runs on high to try again. The igniter then glows for about 17 seconds, the first-stage gas valve opens and a flame must be proven within 4 seconds. The blower then starts at first-stage speed after its heating delay.
When heating ends. The gas valve closes, the inducer runs about 5 more seconds to clear the fumes and the blower runs for the off time set in the control menu. The display returns to IDL, meaning idle. Any air cleaner turns on about 2 seconds after the blower, and a humidifier about 1 second after.
What is normal. Humming, a short wait with no heat, and the blower running after the burners stop.
Safe checks. Replace a dirty filter, make sure the furnace door is on, the power switch is on, and the exhaust and intake pipes outside are clear of snow and nests.
When to call a technician. Code e3.1, repeated shutdowns or any gas smell (leave and call from outside) means calling Aurora Star Tech.
Key times at a glance
| What | How long or how much |
|---|---|
| Ignitor warm-up | about 17 s |
| Flame prove time | 4 s |
| Pressure switch 1 prove time | 60 s |
| Post-purge | about 5 s |
| Typical flame current | 0.75 to 3.0 uA (read as 0.75 to 3 VDC at the FP pads) |
| EAC relay delay | about 2 s after blower starts |
| HUM relay delay | about 1 s after blower starts |
Applies to: S8B1, S8X1 and S8X2 80 percent furnaces
Error codes linked to this step
Questions about the Trane furnace
What is the First-stage gas heating on a Trane furnace?
Trane S8B1, S8X1 and S8X2 are 80 percent efficient gas furnaces. This page follows the first stage of heating, step by step, so each click and hum makes sense.
Is it normal for my Trane furnace to do this?
Humming, a short wait with no heat, and the blower running after the burners stop.
Who can service my Trane furnace near me?
Aurora Star Tech Inc. repairs and services Trane furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.