Updated · by Aurora Star Tech Inc.

A Rheem R96V or 96V two-stage condensing furnace always lights its burners on high fire first, then settles to the heat level your thermostat asks for. This page follows a normal heat call.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

How the Rheem furnace works: Two-stage gas heat call, ignition on high fire and retry

What this is. A Rheem R96V or 96V two-stage condensing furnace always lights its burners on high fire first, then settles to the heat level your thermostat asks for. This page follows a normal heat call.

What happens, in order. When the thermostat (or a communicating thermostat) calls for heat, the control checks that both airflow switches are open. The inducer fan starts on high speed for a 30-second pre-purge. After the airflow switches close, the gas valve opens on the high stage for an 8-second trial, with the spark on for up to 7 seconds. The flame sensor has to prove flame for one second. Twenty seconds later the gas valve moves to the stage the thermostat wants, and the blower starts at the matching low or high speed. If the thermostat is calling for high, nothing changes.

If the flame does not catch. The furnace repeats the sequence up to four times, then enters a one-hour lockout.

When the call ends. The valve closes, the flame goes out, and the inducer runs a 10-second post-purge. The blower then runs out its heat-off delay, set on the control board.

What is normal. A louder start on high fire, a switch to quieter low fire after about 20 seconds, and warm air starting about a minute after the call.

Safe checks. Replace a clogged filter, check the thermostat, furnace switch and breaker, and clear snow from the outside vent pipes. One power reset is fine.

When to call a technician. Lockouts, no heat, or any smell of gas (leave the house and call from outside). Aurora Star Tech services Rheem furnaces across the GTA.

Key times at a glance

WhatHow long or how much
Pre-purge30 s, inducer on high
Trial for ignition8 s
Spark on after valve opensup to 7 s
Stage select / blower start after flame20 s
Post-purge10 s
Ignition attempts4
Lockout1 hour

Applies to: Rheem R96V and 96V series two-stage condensing furnaces

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Questions about the Rheem furnace

What is the Two-stage gas heat call, ignition on high fire and retry on a Rheem furnace?

A Rheem R96V or 96V two-stage condensing furnace always lights its burners on high fire first, then settles to the heat level your thermostat asks for. This page follows a normal heat call.

Is it normal for my Rheem furnace to do this?

A louder start on high fire, a switch to quieter low fire after about 20 seconds, and warm air starting about a minute after the call.

Who can service my Rheem furnace near me?

Aurora Star Tech Inc. repairs and services Rheem furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.