Rheem furnace: Gas heat call, direct spark ignition and retry
The Rheem 90RJ furnace with direct spark ignition lights its burners with an electric spark instead of a hot element. This page explains what you should hear and see on a normal heat call, and what the furnace does if the flame fails to appear.
How the Rheem furnace works: Gas heat call, direct spark ignition and retry
What this is. The Rheem 90RJ furnace with direct spark ignition lights its burners with an electric spark instead of a hot element. This page explains what you should hear and see on a normal heat call, and what the furnace does if the flame fails to appear.
What happens, in order. When the thermostat contacts close, the inducer fan starts and pre-purges the burner area. After the air safety switch confirms airflow, the furnace waits 30 seconds, then the spark igniter energizes and the gas valve opens for an 8-second trial. The flame sensor must prove flame for one second. Twenty seconds after the burners light, the main blower starts. The inducer runs throughout the heat cycle.
If the burners do not light. The valve closes, the spark stops, the inducer runs a 10-second post-purge, and the control confirms the switch has reopened. Then it tries again with a 30-second pre-purge. After the second miss, the blower and inducer run together for 3 minutes before the next attempt. There are four attempts in total, followed by a one-hour soft lockout.
Resetting. Cutting power for 5 to 10 seconds, or turning the thermostat call off and on, restarts the process.
What is normal. Ticking from the spark, a short pause before the burners light, and a wait of about a minute before warm air arrives.
Safe checks. Replace the filter if it is dirty, check the thermostat, breaker and furnace switch, and make sure the outdoor vent pipes are clear. Reset power only once.
When to call a technician. Lockouts that keep coming back or no heat after an hour call for service from Aurora Star Tech. If you smell gas, leave the home and call from outside.
Key times at a glance
| What | How long or how much |
|---|---|
| Pre-purge | 30 s |
| Trial for ignition | 8 s |
| Blower on delay | 20 s after ignition |
| Post-purge | 10 s |
| Self-healing blower/inducer run | 3 min |
| Ignition attempts | 4 |
| Lockout | 1 hour |
Applies to: Rheem 90RJ series (direct spark control)
Questions about the Rheem furnace
What is the Gas heat call, direct spark ignition and retry on a Rheem furnace?
The Rheem 90RJ furnace with direct spark ignition lights its burners with an electric spark instead of a hot element. This page explains what you should hear and see on a normal heat call, and what the furnace does if the flame fails to appear.
Is it normal for my Rheem furnace to do this?
Ticking from the spark, a short pause before the burners light, and a wait of about a minute before warm air arrives.
Who can service my Rheem furnace near me?
Aurora Star Tech Inc. repairs and services Rheem furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.