If your NTI TRX150 boiler cannot light its burner, it does not keep trying forever. This page explains how many times it tries and what happens afterward.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

How the NTI boiler works: Failed ignition and lockout

What this is. If your NTI TRX150 boiler cannot light its burner, it does not keep trying forever. This page explains how many times it tries and what happens afterward.

What happens, in order. The burner fails to light, so the control starts another ignition trial. The trials after the first are not immediate, because the boiler waits in between. After each failed trial the blower runs for about 5 seconds to purge the combustion chamber of unburned gas. If the burner lights on any trial, normal operation simply carries on. If it still has not lit after the fifth trial, which is the first plus four more, the control locks out. The display then shows code 501 or 503.

What a lockout means. A lockout tells you there is a problem with the boiler, its controls or the gas supply. If nobody presses RESET, the boiler tries to reset itself automatically after one hour.

What is normal. A brief extra fan noise between attempts and the occasional single failed attempt on a cold start that clears on its own.

Safe checks. Make sure the gas supply to the house is on and the gas meter has not been shut off, the power switch is on, and the vent pipes outside are clear of snow and debris. You may press RESET once. If it locks out again, stop.

When to call a technician. Right away if a lockout returns. Leave the house and call from outside if you smell gas. Aurora Star Tech can diagnose ignition problems across Vaughan, Toronto and the GTA.

Key times at a glance

WhatHow long or how much
Blower purge after a failed ignition trialabout 5 seconds
Ignition trials before lockoutfive in total (four more after the first)
Automatic reset after lockout if RESET is not pressedone hour

Applies to: TRX150

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Questions about the NTI boiler

What is the Failed ignition and lockout on a NTI boiler?

If your NTI TRX150 boiler cannot light its burner, it does not keep trying forever. This page explains how many times it tries and what happens afterward.

Is it normal for my NTI boiler to do this?

A brief extra fan noise between attempts and the occasional single failed attempt on a cold start that clears on its own.

Who can service my NTI boiler near me?

Aurora Star Tech Inc. repairs and services NTI boilers in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.