KeepRite furnace: Modulating 95% furnace: ignition sequence and retries
KeepRite 9MAE furnaces are modulating: instead of just low and high, they adjust their flame in small steps. They still start the same careful way, with a hot surface igniter, and this page walks through that start-up and what happens if lighting fails.
How the KeepRite furnace works: Modulating 95% furnace: ignition sequence and retries
What this is. KeepRite 9MAE furnaces are modulating: instead of just low and high, they adjust their flame in small steps. They still start the same careful way, with a hot surface igniter, and this page walks through that start-up and what happens if lighting fails.
What happens, in order. When the thermostat calls, the furnace checks that its airflow switches are open, then raises the inducer fan slowly. As the airflow switches close, the control notes how hard the fan is working, which tells it how much resistance the vent pipes have. A 25-second purge clears the chamber, the igniter warms for 17 seconds, and the gas valve opens. Five seconds later the control looks for flame during a 2-second window. Once flame is proven, it trims the inducer speed to match the heat level it started at, slightly down for a medium start and up for a maximum start.
If the flame does not catch. The gas valve closes and the furnace tries again, up to four tries in total, then locks out. The lockout resets by itself after 3 hours or after power to the furnace is switched off and on. If flame ever shows when it should not, gas heating is blocked and the inducer runs at full speed until the flame is gone.
What is normal. A gradual fan ramp-up before ignition, soft clicking, and a second attempt on a cold start.
Safe checks. Replace the filter, close the furnace door, check the thermostat and breaker, and keep outdoor vent pipes clear of snow. One power reset is fine.
When to call. Repeated lockouts, a fault light, or any gas smell, in which case leave and call from outside. Aurora Star Tech services KeepRite furnaces across the GTA.
Key times at a glance
| What | How long or how much |
|---|---|
| Prepurge | 25 s |
| Igniter warm-up | 17 s |
| Flame proving | 2 s |
| Ignition trials | 4 total |
| Lockout auto-reset | 3 hours |
Applies to: ICP (F-G)9MAE modulating 95% furnace
Questions about the KeepRite furnace
What is the Modulating 95% furnace: ignition sequence and retries on a KeepRite furnace?
KeepRite 9MAE furnaces are modulating: instead of just low and high, they adjust their flame in small steps. They still start the same careful way, with a hot surface igniter, and this page walks through that start-up and what happens if lighting fails.
Is it normal for my KeepRite furnace to do this?
A gradual fan ramp-up before ignition, soft clicking, and a second attempt on a cold start.
Who can service my KeepRite furnace near me?
Aurora Star Tech Inc. repairs and services KeepRite furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.