Gree mini-split: Cooling and dry mode (multi-zone)
The Gree Multi21+ is a multi-zone system: one outdoor unit serves several indoor units, each in its own room. This page describes how the outdoor unit behaves in cooling and dry mode, which explains why it keeps running when only some rooms are cool enough.
How the Gree mini-split works: Cooling and dry mode (multi-zone)
What this is. The Gree Multi21+ is a multi-zone system: one outdoor unit serves several indoor units, each in its own room. This page describes how the outdoor unit behaves in cooling and dry mode, which explains why it keeps running when only some rooms are cool enough.
What happens, in order. When any one indoor unit asks for cooling, the outdoor unit opens that room's expansion valve and starts up. The outdoor fan comes on 5 seconds before the compressor and runs fast for the first 3 minutes before settling to its normal speed. Each fan speed is held for at least 80 seconds, so it will not flutter up and down. If some rooms reach their setting and others do not, the compressor keeps running at whatever speed the remaining rooms need, and the satisfied rooms are closed off. Only when every indoor unit is satisfied does the compressor stop, with the outdoor fan running one more minute. The reversing valve is not used in cooling; if you switch over to heating, the system waits until the compressor has been off 2 minutes first. Dry mode starts and stops the same way, with each room's demand limited to 90 percent of its cooling capacity so the air dries gently.
What is normal. A louder outdoor fan for the first few minutes, one room still cooling while another has stopped, and a short pause when changing modes.
Safe checks. Rinse each indoor unit's washable filter, check remote batteries and keep the outdoor unit clear of leaves, snow and storage.
When to call. If one room never cools, an indoor unit shows a code or the outdoor unit will not start, contact Aurora Star Tech.
Key times at a glance
| What | How long or how much |
|---|---|
| Outdoor fan lead | 5 s before compressor |
| Outdoor fan high-speed period | 3 min |
| Minimum time per fan speed | 80 s |
| Outdoor fan run-on | 1 min |
| 4-way valve change delay | 2 min after compressor stop |
Applies to: Gree Multi21+ multi-zone heat pump outdoor units
Questions about the Gree mini-split
What is the Cooling and dry mode (multi-zone) on a Gree mini-split?
The Gree Multi21+ is a multi-zone system: one outdoor unit serves several indoor units, each in its own room. This page describes how the outdoor unit behaves in cooling and dry mode, which explains why it keeps running when only some rooms are cool enough.
Is it normal for my Gree mini-split to do this?
A louder outdoor fan for the first few minutes, one room still cooling while another has stopped, and a short pause when changing modes.
Who can service my Gree mini-split near me?
Aurora Star Tech Inc. repairs and services Gree mini-splits in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.