Gree mini-split: Automatic defrost
In winter, the outdoor unit of your Gree Livo GEN4 builds up frost and clears it with an automatic defrost. This page explains when it starts and what happens.
How the Gree mini-split works: Automatic defrost
What this is. In winter, the outdoor unit of your Gree Livo GEN4 builds up frost and clears it with an automatic defrost. This page explains when it starts and what happens.
What happens, in order. The unit considers defrost after 45 minutes of continuous heating or 90 minutes in total, as long as the outdoor coil is colder than expected for the outdoor air temperature. For example, with air at 41 F or above, a coil at 28.4 F or lower qualifies. Defrost starts 3 minutes after the conditions are met. The indoor fan and compressor stop, and 60 seconds later the outdoor fan stops. After 30 seconds the reversing valve switches, and 30 seconds after that the compressor starts and ramps up to defrost speed. Defrost ends after 10 minutes, or sooner when the outdoor coil reaches 50 F, and the compressor then eases down. Thirty seconds later it stops, and 30 seconds after that the valve switches back to heating. A minute later the compressor and outdoor fan restart, the indoor fan resumes under its anti-cold-air rules, and H1 shows on the display.
What is normal. Steam from the outdoor unit, dripping water, a whooshing sound when the valve switches, and a few minutes without warm air. H1 is a status message, not a fault.
Safe checks. Keep snow, ice and leaves away from the outdoor unit and leave space around it. Make sure the unit is in Heat mode and the filters are clean.
When to call a technician. Thick ice that stays for hours, constant repeated defrost, or no warmth in the house. Aurora Star Tech can help.
Key times at a glance
| What | How long or how much |
|---|---|
| Heating run before defrost | 45 min continuous or 90 min accumulated |
| Delay after conditions met | 3 min |
| Defrost frequency | 70 Hz |
| Maximum defrost time | 10 min |
| Exit frequency | 46 Hz |
Applies to: Gree Livo GEN4 wall mini-split heat pumps 30k-36k
Questions about the Gree mini-split
What is the Automatic defrost on a Gree mini-split?
In winter, the outdoor unit of your Gree Livo GEN4 builds up frost and clears it with an automatic defrost. This page explains when it starts and what happens.
Is it normal for my Gree mini-split to do this?
Steam from the outdoor unit, dripping water, a whooshing sound when the valve switches, and a few minutes without warm air. H1 is a status message, not a fault.
Who can service my Gree mini-split near me?
Aurora Star Tech Inc. repairs and services Gree mini-splits in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.