Goodman furnace: Dual fuel heat pump to gas furnace transition
If your Goodman furnace is paired with a heat pump in a dual fuel setup, the system has to decide which one heats your home. This page explains how it switches between the heat pump and gas furnace in a smart way.
How the Goodman furnace works: Dual fuel heat pump to gas furnace transition
What this is. If your Goodman furnace is paired with a heat pump in a dual fuel setup, the system has to decide which one heats your home. This page explains how it switches between the heat pump and gas furnace in a smart way.
What happens, in order. On a call for heat, the heat pump goes first, provided the outdoor temperature is not so low that it has been locked out. If the call is still unsatisfied after a target running time, the heat pump gets a bit of extra time, and then the system hands over to gas heat. Each hand-over counts as a strike against the heat pump. Once enough strikes pile up, the heat pump is locked out and the furnace becomes the main heat source, running its low stage. While in lockout, if the furnace satisfies the home faster than a set limit, that counts as a strike against the furnace. After enough of those, the lockout is lifted and the heat pump gets another try on the next cycle.
An example. With a 20-minute target and a 20 percent extra allowance, the heat pump gets 4 more minutes, so gas takes over at 24 minutes. With a 15 percent stage-down setting, a furnace that satisfies the house in under 17 minutes counts as a strike.
What is normal. Gas heat starting in the middle of a cold call, the heat pump sitting out for a while, and its return later.
Safe checks. Keep the outdoor unit clear of snow and ice, replace the filter, and set the thermostat to Heat, avoiding large setbacks.
When to call a technician. If the system only ever uses one source or heat is poor. Aurora Star Tech can tune dual fuel systems.
Key times at a glance
| What | How long or how much |
|---|---|
| Example target runtime | 20 minutes |
| Example stage up 20% | extra 4 minutes, switch to gas at 24 minutes |
| Example stage down 15% | furnace satisfying in under 17 minutes counts as a strike |
Applies to: Communicating or fossil fuel heat pump with gas furnace
Questions about the Goodman furnace
What is the Dual fuel heat pump to gas furnace transition on a Goodman furnace?
If your Goodman furnace is paired with a heat pump in a dual fuel setup, the system has to decide which one heats your home. This page explains how it switches between the heat pump and gas furnace in a smart way.
Is it normal for my Goodman furnace to do this?
Gas heat starting in the middle of a cold call, the heat pump sitting out for a while, and its return later.
Who can service my Goodman furnace near me?
Aurora Star Tech Inc. repairs and services Goodman furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.