Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Goodman-Amana-Daikin furnace: Gas heat call and shutdown

Updated · by Aurora Star Tech Inc.

A Goodman or Amana GM9S80 or GC9S80 is a single-stage, 80 percent efficiency gas furnace. When the thermostat asks for heat, it follows a set order of safety checks before the burners light. This page explains each step and shutdown.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

How the Goodman-Amana-Daikin furnace works: Gas heat call and shutdown

What this is. A Goodman or Amana GM9S80 or GC9S80 is a single-stage, 80 percent efficiency gas furnace. When the thermostat asks for heat, it follows a set order of safety checks before the burners light. This page explains each step and shutdown.

What happens, in order. The control board watches its safety circuits at all times and checks them again when the thermostat asks for heat. The inducer fan starts, and when the airflow switch confirms good draft, the inducer keeps running for a pre-purge. The igniter then warms up, and at the end of that warm-up the gas valve opens. The control looks for a flame within 4 seconds, and gas only continues if the flame is proven. About 30 seconds after, the circulating blower starts pushing warm air into your home. When the thermostat is satisfied, the gas valve closes, the inducer runs for 15 more seconds to clear the chamber, and the blower continues for a cool-down chosen by the installer, anywhere from 90 to 180 seconds, then stops.

If the flame does not catch. The control tries up to three times in one call, then locks out and shows E0.

What is normal. A short delay before the flame, the inducer whirring first, a clicking sound, and a blower that runs on after the burners go out.

Safe checks. Replace a dirty filter, close the furnace door fully, make sure the thermostat and breaker are on, and clear snow or nests from the outside vent. You may switch power off for ten seconds, and on again, once. If you smell gas, leave the house and call from outside.

When to call a technician. An E0 lockout, repeated starts that fail, or a furnace that shuts off before the house warms. Aurora Star Tech can help.

Key times at a glance

WhatHow long or how much
Trial for flame check4 s
Blower on delay30 s
Post-purge15 s
Blower off delay90, 120, 150 or 180 s
Ignition retries3 total, then lockout

Applies to: Goodman GM9S80, GC9S80; Amana AM9S80, AC9S80

Error codes linked to this step

Goodman code E0

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Questions about the Goodman-Amana-Daikin furnace

What is the Gas heat call and shutdown on a Goodman-Amana-Daikin furnace?

A Goodman or Amana GM9S80 or GC9S80 is a single-stage, 80 percent efficiency gas furnace. When the thermostat asks for heat, it follows a set order of safety checks before the burners light. This page explains each step and shutdown.

Is it normal for my Goodman-Amana-Daikin furnace to do this?

A short delay before the flame, the inducer whirring first, a clicking sound, and a blower that runs on after the burners go out.

Who can service my Goodman-Amana-Daikin furnace near me?

Aurora Star Tech Inc. repairs and services Goodman-Amana-Daikin furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Furnace Repair

647-657-2977