Carrier heat pump: Single-stage communicating heat pump: demand defrost, Auto interval and Quiet Shift-2
The Carrier Infinity single-stage heat pump decides for itself when it needs a defrost, and adjusts how often it checks based on how the last defrost went. This page explains the logic and the optional Quiet Shift-2 feature.
How the Carrier heat pump works: Single-stage communicating heat pump: demand defrost, Auto interval and Quiet Shift-2
What this is. The Carrier Infinity single-stage heat pump decides for itself when it needs a defrost, and adjusts how often it checks based on how the last defrost went. This page explains the logic and the optional Quiet Shift-2 feature.
What happens, in order. The unit is set to check at 30, 60, 90 or 120 minute intervals, or on Auto, where the last defrost's length picks the next interval: under 3 minutes gives 120, 3 to 5 gives 90, 5 to 7 gives 60, and over 7 gives 30. As the interval nears, the board looks at the coil. If the coil has sat at or below 32 F for 4 minutes, it defrosts, otherwise the timer resets. The first interval after power-up is 30 minutes, and it only runs when outdoor air is below 50 F. Defrost ends when the coil reaches 65 F or after 10 minutes. With Quiet Shift-2, the compressor pauses 70 seconds at the start and 60 seconds at the end to soften noise.
What is normal. Steam, dripping, a fan that stops for a few minutes and cooler air briefly. A basic thermostat may finish a held defrost on the next heat call.
Safe checks. Clear snow, ice and leaves from around the outdoor unit and make sure the thermostat is on Heat.
When to call. If ice keeps building up or heat is weak, Aurora Star Tech can inspect the sensor and settings.
Key times at a glance
| What | How long or how much |
|---|---|
| Interval options | 30 / 60 / 90 / 120 min |
| First interval after power-up | 30 min |
| Defrost demand | coil at or below 32 F for 4 min |
| Defrost allowed below | 50 F outdoor |
| Defrost end | 65 F coil or 10 min |
| Quiet Shift-2 | 70 s off at start, 60 s off at end |
Applies to: Carrier / Bryant / Payne split heat pumps with HK32EA defrost control boards (Performance Series and Comfort Series)
Questions about the Carrier heat pump
What is the Single-stage communicating heat pump: demand defrost, Auto interval and Quiet Shift-2 on a Carrier heat pump?
The Carrier Infinity single-stage heat pump decides for itself when it needs a defrost, and adjusts how often it checks based on how the last defrost went. This page explains the logic and the optional Quiet Shift-2 feature.
Is it normal for my Carrier heat pump to do this?
Steam, dripping, a fan that stops for a few minutes and cooler air briefly. A basic thermostat may finish a held defrost on the next heat call.
Who can service my Carrier heat pump near me?
Aurora Star Tech Inc. repairs and services Carrier heat pumps in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.