Carrier furnace: Single-stage 80% furnace: heating cycle, blower delays and shutdown
Once your Carrier 58SB furnace has lit its burners, it starts the blower after a short delay and keeps it running after the flame goes out, so you get the heat from the furnace. This page explains the timing.
How the Carrier furnace works: Single-stage 80% furnace: heating cycle, blower delays and shutdown
What this is. Once your Carrier 58SB furnace has lit its burners, it starts the blower after a short delay and keeps it running after the flame goes out, so you get the heat from the furnace. This page explains the timing.
What happens, in order. After the flame is confirmed, the blower starts on heat speed 25 seconds after the gas valve opens, and the burners run until the thermostat is satisfied. When the thermostat stops asking for heat, the gas valve closes, the inducer fan runs for a short 5 second clean-out, and then it stops. The blower continues for a set cool-down, chosen by the installer at 90, 120, 150 or 180 seconds, with 120 seconds as the factory setting, and then stops. If power fails in the middle of a heat call, the furnace runs the blower alone for 90 seconds after power returns, with the display showing code 12, and then answers the thermostat normally.
What is normal. Warm air arriving a little after the burners light, a blower that keeps running for a couple of minutes after the heat stops, and code 12 appearing after a power cut.
Safe checks. Keep the filter clean and vents open. If air from the vents seems too cool or the blower runs endlessly, check that the thermostat fan setting is on Auto rather than On.
When to call. If the blower never starts, never stops, or the home stays cold, Aurora Star Tech can service your furnace.
Key times at a glance
| What | How long or how much |
|---|---|
| Blower-on delay | 25 s |
| Inducer post-purge | 5 s |
| Blower-off delay options | 90 / 120 / 150 / 180 s |
| Blower-off delay factory | 120 s |
| Blower-only run after power-up | 90 s |
Applies to: Carrier 58SB0A / 58SB1A 80% single-stage gas furnace
Error codes linked to this step
Questions about the Carrier furnace
What is the Single-stage 80% furnace: heating cycle, blower delays and shutdown on a Carrier furnace?
Once your Carrier 58SB furnace has lit its burners, it starts the blower after a short delay and keeps it running after the flame goes out, so you get the heat from the furnace. This page explains the timing.
Is it normal for my Carrier furnace to do this?
Warm air arriving a little after the burners light, a blower that keeps running for a couple of minutes after the heat stops, and code 12 appearing after a power cut.
Who can service my Carrier furnace near me?
Aurora Star Tech Inc. repairs and services Carrier furnaces in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.