Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Bosch heat pump: Demand defrost

Updated · by Aurora Star Tech Inc.

On a cold day the outdoor coil of your Bosch IDS heat pump slowly gathers frost, the way a freezer does. The unit is designed to notice this on its own and melt the ice away, and this page explains how it decides, what you will see and how it finishes.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

How the Bosch heat pump works: Demand defrost

What this is. On a cold day the outdoor coil of your Bosch IDS heat pump slowly gathers frost, the way a freezer does. The unit is designed to notice this on its own and melt the ice away, and this page explains how it decides, what you will see and how it finishes.

What happens, in order. The unit compares the temperature of its outdoor coil with the outside air. If the gap stays wide enough for 3 minutes, frost is assumed and a defrost begins. The gap it looks for depends on the weather: 18 degrees F when the air is 39 F or warmer, 16 degrees at 30 F or warmer, and 14 degrees at 19 F or warmer. In very cold air it also counts running time, starting a defrost after 80 minutes of compressor work. Run-time backups exist as well: after 4 hours of heating when the air is below 23 F, or 2 hours in the mild-cold range. A low pressure reading can start one too. While it defrosts, the outdoor display shows "dF". It ends once the coil warms to about 64 F for a minute, or after 8 minutes, whichever is first.

What is normal. White vapour rising off the unit, dripping or running water, a brief whoosh as the system changes direction, and slightly cooler air from your vents for a few minutes.

Safe checks. Keep snow, ice and leaves cleared from around the outdoor unit and confirm the thermostat is set to Heat with a clean filter indoors.

When to call a technician. If the unit stays buried in ice, seems to defrost nonstop, or the house will not warm up, Aurora Star Tech can inspect it for you across Vaughan, Toronto and the GTA.

Key times at a glance

WhatHow long or how much
Delta T, air 39F or above18F
Delta T, air 30F or above16F
Delta T, air 19F or above14F
Delta T hold time3 min
Run time, air below 19F and coil below 9F80 min
Minimum run time, air below 23F4 h
Defrost endCoil 64F for 1 min, or 8 min max
Low-pressure defrost triggerBelow 82F saturation for 20 min

Applies to: Bosch IDS inverter heat pump condensing units

Error codes linked to this step

Bosch code dF

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Questions about the Bosch heat pump

What is the Demand defrost on a Bosch heat pump?

On a cold day the outdoor coil of your Bosch IDS heat pump slowly gathers frost, the way a freezer does. The unit is designed to notice this on its own and melt the ice away, and this page explains how it decides, what you will see and how it finishes.

Is it normal for my Bosch heat pump to do this?

White vapour rising off the unit, dripping or running water, a brief whoosh as the system changes direction, and slightly cooler air from your vents for a few minutes.

Who can service my Bosch heat pump near me?

Aurora Star Tech Inc. repairs and services Bosch heat pumps in Vaughan, Toronto and across the GTA. Call (647) 657-2977 or book a service call online.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency HVAC Service

647-657-2977