KeepRite Air Conditioner: Checking OAT and OCT thermistors – KeepRite C4A3/CXA6

Updated · by Aurora Star Tech Inc.

Checking OAT and OCT thermistors - KeepRite C4A3/CXA6 on a KeepRite air conditioner: Codes 53, 55 and 56 on the KeepRite C4A3 or CXA6 point to the outdoor air thermistor (OAT) or the outdoor coil thermistor (OCT). These are simple sensors, and you can check them with an ohmmeter. A thermistor is a resistor that changes value with temperature, so you compare your reading to the curve for the ambient. The usual trouble is a sensor that has been moved from its factory spot. If a sensor fails, the board falls back to default operation, so the system keeps running but not optimally.

Homeowner with a air conditioner problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: KeepRite C4A3/CXA6 AC with outdoor control board

Common causes of checking oat and oct thermistors - keeprite c4a3/cxa6

  • Failed thermistor
  • Sensor moved from its factory location
  • Loose OCT clamp
  • Damaged wire or plug at the board

How to fix checking oat and oct thermistors - keeprite c4a3/cxa6: step by step

  1. Unplug the thermistor assembly from the board, power off first
  2. Measure each thermistor and compare with the resistance curve (about 16,000 ohms at 60°F)
  3. Check the OAT is locked in its keyhole in the control box shelf
  4. Check the OCT (C4A3 sizes 24 and 30) is fastened tightly on the liquid tube, a loose clamp reads the wrong temperature
  5. Inspect the wire and plug for damage
  6. Replace any sensor out of range
  7. The board falls back to default operation if a sensor fails, so do not ignore the code
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: KeepRite Air Conditioner codes

Models

KeepRite *CA/*CH Two-Stage Communicating

*CA624*CA636*CA648*CA660*CA924*CA936*CA948*CA960

KeepRite *SA/*SH Single-Stage Communicating

*SA5*SA6

KeepRite C4A3/CXA6 AC

C4A3CXA6

Source: KeepRite/ICP C4A3/H4A3/T4A3/CXA6 Installation Instructions 421 01 5103 05, Temperature Thermistors p.16, Fig. 17-18 p.14 and p.18. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.