Weil-McLain Boiler: Verify the boiler model setting before startup
Verify the boiler model setting before startup on a Weil-McLain boiler: The U-Control model setting must match the rating plate. A wrong model setting can cause severe injury, death or property damage. The model is also shown on the display at power-up.
Applies to: All Ultra models
How to fix verify the boiler model setting before startup: step by step
- Read the model on the boiler rating plate.
- Check the BOILER MODEL setting in the contractor menu (80, 105, 155, 230, 299 or 399).
- Change the setting if it does not match.
- Confirm the model shown on the display at power-up.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: Weil-McLain Ultra Series 4 boiler manual, p. 99, p. 102 and p. 104. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.