Weil-McLain Boiler: Verify propane conversion and blower model
Verify propane conversion and blower model on a Weil-McLain boiler: Boilers ship ready for natural gas only. For propane, confirm the conversion. On the 199, confirm the blower model is selected.
Applies to: ECO Tec Series 3 80/110/150/199
How to fix verify propane conversion and blower model: step by step
- For propane, verify the boiler was converted per page 19 before startup.
- On the 199, check the blower label (Figure 158, page 177).
- Confirm the correct model is selected on the Boiler Settings Blower Model screen.
- Verify this again after a factory reset, control replacement or blower replacement.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 133. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.