Weil-McLain Boiler: Standard and optional equipment
Standard and optional equipment on a Weil-McLain boiler: Standard equipment differs for EG/PEG boilers, EG water boilers and EG/PEG steam boilers. Use this list to confirm what should be on a boiler when servicing it.
Applies to: EG and PEG Series 7 boilers
How to fix standard and optional equipment: step by step
- EG/PEG boilers: combination gas valve for 24 volt, rollout thermal fuse element, spill switch, and on the highest efficiency models a PID intermittent electronic ignition with automatic vent damper.
- EG water boilers: Unity-CI ignition module, temperature/LWCO sensor, built-in air eliminator, 30 PSI relief valve, combination pressure temperature gauge, and 50 VA transformer.
- EG/PEG steam boilers: 15 PSI relief valve, steam pressure gauge, high-limit pressure control, syphon, gauge cocks, gauge glass, probe-type low-water cutoff, and 40 VA transformer.
- Standard on all: factory-assembled section block, insulated extended jacket, draft hood, aluminized steel burners, non-linting pilot burner, heater cover plates (for boilers with tankless heater openings), control wire, and electrical junction box.
- EG additional equipment: water tankless heater kits and steam tankless heater kits (EG-35 to EG-75).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: EG / PEG Series 7 Natural Gas-Fired Boiler Manual, p. 90. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.