Weil-McLain Boiler: Sizing system and zone circulator flow
Sizing system and zone circulator flow on a Weil-McLain boiler: Flow in gpm equals heat load in Btuh divided by (temperature drop x 500). For a 20°F drop, flow equals MBH divided by 10. The circulator must deliver this flow against the calculated head loss.
Applies to: System and zone circulators supplied by installer
How to fix sizing system and zone circulator flow: step by step
- Calculate flow: FLOW = BTUH / (TD x 500).
- Example: 210,000 Btuh load with 20°F drop gives about 20 gpm.
- Find pipe size and head loss using accepted engineering methods.
- Select a circulator that meets the flow at that head loss.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: ECO Tec Series 3 boiler manual, p. 59. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.