Weil-McLain Boiler: Single combustion air opening and large space exception
Single combustion air opening and large space exception on a Weil-McLain boiler: One combined opening or no openings can be used in some cases, but only under the conditions below.
Applies to: Ultra direct exhaust boiler rooms
How to fix single combustion air opening and large space exception: step by step
- For a single opening, make sure it opens directly to outdoors, or to a space that opens directly to outdoors, not to an interior space.
- Put the top of the single opening within 12 inches of the ceiling.
- Make the free area at least equal to the total area of all equipment vent connectors in the space.
- For large spaces, total the input of all appliances in MBH and multiply by 50 to get the minimum room volume in cubic feet.
- Use no openings only if the room volume meets that minimum and the building is not of tight construction.
- Example: 1500 MBH with an 8 foot ceiling needs 60,000 cubic feet (50 x 1500 x 8).
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Ultra Series 4 boiler manual, p. 85. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.