Weil-McLain Boiler: Sidewall direct exhaust termination assembly
Sidewall direct exhaust termination assembly on a Weil-McLain boiler: Sidewall terminations use a down-turned 90-degree elbow and vent manufacturer stop plates so the vent cannot be pushed inward.
Applies to: SVF 1500-3000 Series 1, direct exhaust sidewall
How to fix sidewall direct exhaust termination assembly: step by step
- Cut the vent hole at least 3/8 in larger than the vent pipe diameter for combustible construction, or as the vent maker specifies.
- Insert a corrosion-resistant metal thimble in the hole.
- Install vent manufacturer stop plates with holes just larger than the vent pipe; get them only from the vent manufacturer.
- Insert the last vent pipe length from outside until its female shoulder rests on the outer stop plate.
- Insert the down-turned 90-degree termination elbow and install a bird screen in its open end.
- Seal exterior openings thoroughly with exterior caulk.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF Series 1 boiler manual, p. 36, p. 37. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.