Weil-McLain Boiler: Return water temperature and low-temperature systems
Return water temperature and low-temperature systems on a Weil-McLain boiler: Figures 16 and 17 apply only when return water is at least 130°F. Systems with low return temperature need bypass piping to prevent condensation and corrosion.
Applies to: Low-temperature and radiant systems
How to fix return water temperature and low-temperature systems: step by step
- Use the Figure 16 or 17 piping only for systems designed for at least 130°F return water.
- For converted gravity systems, radiant systems or other low-return systems, install bypass piping (page 22).
- If the system has radiant circuits, add piping and controls to regulate the supply temperature to them.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: EG/PEG Series 7 boiler manual, p. 21-22. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.