Weil-McLain Boiler: Relief valve installation
Relief valve installation on a Weil-McLain boiler: Install the relief valve only in the tapping on top of the boiler, in the vertical position. The valve may discharge large amounts of steam or hot water, so the discharge line is mandatory.
Applies to: EG/PEG steam boilers
How to fix relief valve installation: step by step
- Clean the valve inlet and all connections; remove foreign matter.
- Mount the relief valve vertically, connected directly to the top tapping designated in the manual.
- Use pipe compound sparingly, or tape, on external threads only.
- Use a proper wrench on the wrench pads only; do not use a pipe wrench on the valve body.
- Pipe the discharge from the outlet to a safe point with no valve in between.
- Make sure the discharge line drains fully and is independently supported and anchored.
- End the discharge freely to atmosphere where it is visible and cannot freeze.
- Use schedule 40 metal pipe, at least the valve outlet size over its full length. Do not use schedule 80 or extra strong pipe.
- Do not cap, plug or obstruct the discharge pipe outlet.
- If the discharge is piped upward, provide a condensate drain in the elbow below the vertical run.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: EG/PEG Series 7 boiler manual, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.