Weil-McLain Boiler: Relief valve and pressure/temperature gauge limits

Updated · by Aurora Star Tech Inc.

Relief valve and pressure/temperature gauge limits on a Weil-McLain boiler: The maximum allowed relief valve setting is 160 PSIG and the boiler ships with a 30 PSIG relief valve. The gauge shipped with the boiler reads to 75 psig and meets ASME requirements only up to a 50 psig relief valve. A higher-rated relief valve needs a gauge with a higher range, and a gauge needing a larger tapping than the 1/4 inch NPT supply tap needs an extra tap placed before any isolation valve.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: All SVF 1500-3000 models

How to fix relief valve and pressure/temperature gauge limits: step by step

  1. Never install a relief valve rated above 160 PSIG.
  2. For a relief valve above 50 psig, fit a P/T gauge with a higher pressure range.
  3. If a larger gauge tapping is needed, add the tap in the near-boiler piping before any isolation valve.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More commissioning tips for boiler

Source: SVF 1500-3000 Series 1 boiler manual, p. 12. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.