Weil-McLain Boiler: Read pilot flame sense value
Read pilot flame sense value on a Weil-McLain boiler: The Advanced Menu shows the pilot flame signal the control measures. A value of 60 or higher means no flame. A good flame reads below 60, and a stronger flame gives a lower number.
Applies to: EG water boilers, pilot ignition
How to fix read pilot flame sense value: step by step
- Open the Advanced Menu.
- Go to Diagnostics, then Inputs & Outputs.
- Select Flame Sense to read the pilot flame value.
- Compare the reading with the threshold: 60 is no flame, and lower values mean better flame quality.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More service & test modes tips for boiler
Source: EG / PEG Series 7 Boiler Manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.