Weil-McLain Boiler: Pitch, support and clearance of vent and air piping
Pitch, support and clearance of vent and air piping on a Weil-McLain boiler: Correct slope and support keep condensate draining back to the boiler and keep the pipe away from combustibles.
Applies to: Direct vent piping
How to fix pitch, support and clearance of vent and air piping: step by step
- Slope vent and air piping continuously toward the boiler at least 1/4 inch per foot of run.
- Avoid any sags along the run.
- Keep at least 3/16 inch clearance between vent pipe and any combustible wall or material.
- Install pipe supports as shown in the figures for the termination type.
- Seal wall and floor penetrations per local code.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: Ultra Series 4 boiler manual, p. 82. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.