Weil-McLain Boiler: Network mode selection on first power-up
Network mode selection on first power-up on a Weil-McLain boiler: The first screen after power-up sets whether the boiler works alone or in a multi-boiler network. Only one master is allowed per multi-boiler system.
Applies to: ECO Tec Series 3 control configuration
How to fix network mode selection on first power-up: step by step
- For a stand-alone boiler choose SINGLE BOILER.
- For a multi-boiler network, set one boiler as ON NETWORK AS MASTER. The master controls firing rate and burner-on commands for the network.
- Set the other boilers as ON NETWORK AS SHADOW. They follow the master for network calls for heat and control themselves for local calls for heat.
- Press the right arrow to continue after selecting.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: ECO Tec Series 3 boiler manual, p. 100. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.