Weil-McLain Boiler: Manual Test Mode for pump voltage and firing rate
Manual Test Mode for pump voltage and firing rate on a Weil-McLain boiler: Manual Test Mode shows live readings and lets you force the firing rate. It is also used to save the variable pump max and min voltages.
Applies to: Evergreen Series 2 with variable speed pump output
How to fix manual test mode for pump voltage and firing rate: step by step
- Open PUMP SETTINGS from the contractor menus and select Manual Test.
- Read status, inputs, modulation source, temperatures, blower signal and speed, flame signal, and pump volts on the screen.
- To set the max pump voltage, force rate to HIGH and save as MAX VOLTS.
- To set the min pump voltage, force rate to LOW and save as the min voltage.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More service & test modes tips for boiler
Source: Weil-McLain Evergreen Series 2 advanced manual, p. 73. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.