Updated · by Aurora Star Tech Inc.

Manual Test Mode for pump voltage and firing rate on a Weil-McLain boiler: Manual Test Mode shows live readings and lets you force the firing rate. It is also used to save the variable pump max and min voltages.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Evergreen Series 2 with variable speed pump output

How to fix manual test mode for pump voltage and firing rate: step by step

  1. Open PUMP SETTINGS from the contractor menus and select Manual Test.
  2. Read status, inputs, modulation source, temperatures, blower signal and speed, flame signal, and pump volts on the screen.
  3. To set the max pump voltage, force rate to HIGH and save as MAX VOLTS.
  4. To set the min pump voltage, force rate to LOW and save as the min voltage.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More service & test modes tips for boiler

Source: Weil-McLain Evergreen Series 2 advanced manual, p. 73. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.