Weil-McLain Boiler: Manifolded gas supply for multiple boilers
Manifolded gas supply for multiple boilers on a Weil-McLain boiler: Layout rules when several boilers share one gas line.
Applies to: SVF 1500-3000 multiple boiler gas supply
How to fix manifolded gas supply for multiple boilers: step by step
- Size the gas piping as for a single boiler, using the total input of all appliances.
- At each boiler, install a manual shutoff gas valve, a union, and a sediment trap at least 3 in below the tee.
- Make sure minimum pressure at each boiler is 3.5 in w.c. with all connected appliances firing.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: SVF Series 1 boiler manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.