Updated · by Aurora Star Tech Inc.

Manifolded combustion air sizing for multiple boilers on a Weil-McLain boiler: Multiple SVF boilers can share a common combustion air manifold. Only air piping may be combined; Category IV vent piping must never be combined.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SVF 1500-3000 Series 1, multiple boilers

How to fix manifolded combustion air sizing for multiple boilers: step by step

  1. Size the duct at least 1 sq in per 2,000 Btuh of total connected boiler input.
  2. Set minimum free area in the duct (after louver restriction) at 1 sq in per 2,000 Btuh, or divide total MBH by 2.
  3. Example: 3,000 MBH total input gives 1,500 sq in minimum combined air duct.
  4. Never combine Category IV vent piping; flue gas leakage and component damage can result.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More other tips for boiler

Source: Weil-McLain SVF Series 1 boiler manual, p. 38. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.