Updated · by Aurora Star Tech Inc.

LWCO TEST button check on a Weil-McLain boiler: Use the LWCO TEST button on the control to confirm the low water cutoff shuts the burners down and restarts them.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: EG and PEG Series 7 boilers with Unity-CI control

How to fix lwco test button check: step by step

  1. With the burners operating, press and hold the LWCO TEST button on the control.
  2. Confirm the burners go off, the circulator keeps running and LWCO is displayed.
  3. Release the LWCO TEST button and confirm the ignition sequence resumes.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More service & test modes tips for boiler

Source: Weil-McLain EG/PEG Series 7 Boiler Manual, p. 65. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.