Weil-McLain Boiler: Large space exception for combustion air openings
Large space exception for combustion air openings on a Weil-McLain boiler: No combustion air openings are needed if the space volume is at least 50 cubic feet per 1,000 Btuh of all appliances in the space and the building is not tight construction.
Applies to: SVF 1500-3000 Series 1
How to fix large space exception for combustion air openings: step by step
- Total the input of all appliances in MBH (thousands of Btuh).
- Multiply the total by 50 to get the minimum room volume in cubic feet.
- Confirm the building is not tight construction.
- Example from manual: 1500 MBH with 8 ft ceiling needs 50 x 1500 = 75,000 cubic feet.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: Weil-McLain SVF Series 1 boiler manual, p. 33, p. 39. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.