Weil-McLain Boiler: Key boiler components and what they do

Updated · by Aurora Star Tech Inc.

Key boiler components and what they do on a Weil-McLain boiler: Reference for the main parts a technician will see on the ECO Tec Series 3 boiler. Item numbers match the manual's component drawing.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec Series 3 80/110/150/199 boilers

How to fix key boiler components and what they do: step by step

  1. Blower (item 3): pulls air through the silencer and venturi and pushes it to the burner through the cover plate.
  2. Gas valve (item 4): references cabinet pressure and opens gas flow when the control applies power. It has an on/off switch for shutdown or service.
  3. Venturi (item 6): creates negative pressure to draw gas into the air stream before the blower.
  4. Boiler circulator (item 7): moves hot water from the boiler to the heating system or the brazed plate heat exchanger.
  5. Boiler out dual sensor (item 8): controls firing rate to hit the outlet target temperature.
  6. Boiler in sensor (item 9): control may reduce input if the in/out temperature difference is too large.
  7. Air pressure switch (item 19): monitors maximum flue pressure.
  8. Flue gas temperature sensor (item 30): control shuts the boiler down if flue gas gets too hot.
  9. Ignition electrode/flame sensor (item 28): high voltage across the electrode creates the spark; after ignition it reads the flame signal.
  10. Transformer (item 31): 120V to 24V for low voltage controls. Do not splice wiring into it.
  11. Condensate tube (item 24) and condensate trap assembly (item 25): field-installed trap connects to the condensate tube.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More other tips for boiler

Source: ECO Tec Series 3 boiler manual, p. 8. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.