Weil-McLain Boiler: Input derate for vent length and altitude
Input derate for vent length and altitude on a Weil-McLain boiler: Input de-rates automatically as vent/air pipe length increases because of pipe pressure loss. Use the derate table for the maximum length. For shorter runs: derate = listed % times vent length divided by 100 (199 with 2 in venting: 13 % times vent length divided by 50). For altitude from sea level to 2,000 ft, no change is needed; the boiler derates itself about 4 % per 1,000 ft above sea level.
Applies to: ECO Tec Series 3 boilers
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 Condensing Gas Boiler Boiler Manual, p. 184. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.