How priority timing and boost work on a Weil-McLain boiler: BOOST TIME raises the target up to 10°F each time a call for heat lasts longer than the set time, capped at MAX TARGET TEMP. SYSTEM OFF DIFF is how far above target the water must rise to turn the boiler off. SYSTEM ON DIFF is how far below target it must drop before network modulation starts. BOILER ON/OFF DIFF set the boiler's own cycling around target or Boiler Max. MAX ON TIME limits how long the boiler runs on a priority while another priority is calling. MIN ON TIME holds the boiler on a priority before it can drop to a lower one; a new higher priority overrides it immediately.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec Series 3 priority menus

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More other tips for boiler

Source: ECO Tec Series 3 boiler manual, p. 120-121. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977