Weil-McLain Boiler: Force a firing rate for testing
Force a firing rate for testing on a Weil-McLain boiler: Manual Test Mode lets you force a modulation rate during a call for heat. Return it to auto afterward.
Applies to: Evergreen Pro Series 2 boilers
How to fix force a firing rate for testing: step by step
- Open DIAGNOSTICS and go to Manual Test Mode.
- Set Force Rate to the rate needed for the test.
- When testing is finished, set Force Rate back to auto.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More service & test modes tips for boiler
Source: Series 2 Advanced Manual 550-100-581, p. 85. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.