Weil-McLain Boiler: Fill the condensate trap before operation
Fill the condensate trap before operation on a Weil-McLain boiler: The condensate trap must hold water whenever the boiler runs, otherwise flue gas can escape through the condensate drain.
Applies to: Ultra Series 4 condensate system
How to fix fill the condensate trap before operation: step by step
- Loosen the hose clamp at the right end of the condensate trap, at the PVC reducing elbow.
- Slide the trap hose off the elbow.
- Fill the trap with fresh water to within an inch of the hose end.
- Reconnect the hose to the elbow and tighten the clamp.
- If the boiler has been out of service a long time, prime the trap by pouring water into the outlet tee while restricting flow in the drain tube.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: Weil-McLain Ultra Series 4 boiler manual, p. 37. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.