Weil-McLain Boiler: Combustion adjustment screw directions

Updated · by Aurora Star Tech Inc.

Combustion adjustment screw directions on a Weil-McLain boiler: Use the throttle screw for high fire and the offset screw for low fire. Adjust in the direction that changes CO2 as needed.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ECO Tec 80/110/150/199 gas valve

How to fix combustion adjustment screw directions: step by step

  1. Throttle screw: turn counterclockwise to increase CO2, clockwise to decrease CO2.
  2. Offset screw (80 and 110 only, under sealed cap): turn clockwise to increase CO2, counterclockwise to decrease CO2.
  3. Adjust high fire first with the throttle screw, then force low fire and adjust the offset screw.
  4. Reinstall the cap over the offset screw after adjusting.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More service & test modes tips for boiler

Source: ECO Tec Series 3 Boiler Manual, p. 22-23. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.