Weil-McLain Boiler: Circulator flow rate formula
Circulator flow rate formula on a Weil-McLain boiler: Size circulators from the flow needed for the wanted temperature change. Use the flow formula, or the shortcut for a 20 °F drop.
Applies to: Ultra Series 4 boilers, space heating circuits
How to fix circulator flow rate formula: step by step
- Flow (gpm) = BTUH / (TD x 500), where TD is the temperature rise or drop in °F.
- Example: 210,000 Btuh at a 20 °F drop gives 21 gpm.
- Shortcut for a 20 °F drop: flow (gpm) = MBH / 10.
- Example: 35,000 Btuh gives 35 / 10 = 3.5 gpm.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
More commissioning tips for boiler
Source: Ultra Series 4 boiler manual, p. 10. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.