Updated · by Aurora Star Tech Inc.

Circulator flow rate formula on a Weil-McLain boiler: Size circulators from the flow needed for the wanted temperature change. Use the flow formula, or the shortcut for a 20 °F drop.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Ultra Series 4 boilers, space heating circuits

How to fix circulator flow rate formula: step by step

  1. Flow (gpm) = BTUH / (TD x 500), where TD is the temperature rise or drop in °F.
  2. Example: 210,000 Btuh at a 20 °F drop gives 21 gpm.
  3. Shortcut for a 20 °F drop: flow (gpm) = MBH / 10.
  4. Example: 35,000 Btuh gives 35 / 10 = 3.5 gpm.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More commissioning tips for boiler

Source: Ultra Series 4 boiler manual, p. 10. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.