Weil-McLain Boiler: Check valve on DHW mixing valve outlet
Check valve on DHW mixing valve outlet on a Weil-McLain boiler: Reverse flow can open the flow switch after a draw ends, so a check valve is required.
Applies to: Combi DHW piping
How to fix check valve on dhw mixing valve outlet: step by step
- Install a field supplied check valve on the outlet of the mixing valve.
- Confirm the flow switch does not activate after the cold draw ends.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec Series 3 boiler manual, p. 49. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.