Updated · by Aurora Star Tech Inc.

Boiler receptacle and output ratings on a Weil-McLain boiler: Electrical limits for the on-board receptacle and the 120 VAC outputs.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Evergreen Pro Series 2 boilers

How to fix boiler receptacle and output ratings: step by step

  1. The boiler right-side receptacle is rated 2.0 A max at 120 VAC. It can power a condensate pump.
  2. Each circulator output is rated 2.0 A max. The 120 VAC auxiliary outputs are also limited to 2.2 A.
  3. For any voltage other than 120 VAC, or for loads above these ratings, use an external relay.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More other tips for boiler

Source: Weil-McLain Series 2 advanced manual 550-100-581/0325, p. 48. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.