Weil-McLain Boiler: Approved vent and air materials and assembly rules
Approved vent and air materials and assembly rules on a Weil-McLain boiler: Use only materials approved for this boiler. Mixing manufacturers, using the wrong plastics, or insulating plastic vent pipe can cause failure.
Applies to: ECO Tec Series 3 vent and air piping materials
How to fix approved vent and air materials and assembly rules: step by step
- Use only the materials in Figure 31 (PVC, PVC-DWV, CPVC, ABS for intake only, polypropylene from Simpson-Duravent or Centrotherm, and AL29-4C stainless from approved makers).
- Use cement and primer suited to the piping material.
- Do not mix pipe from different manufacturers unless using an adapter made for that purpose.
- Use a locking collar on every polypropylene joint.
- Do not use cellular core PVC, cellular core CPVC or Radel (polyphenolsulfone) in venting.
- Do not cover plastic vent pipe or fittings with thermal insulation.
- Use the boiler's 3" 3-in-1 vent adapter for 3" PVC, CPVC, PVC-DWV, Simpson-Duravent AL29-4C, and Simpson-Duravent or Centrotherm polypropylene. The air inlet adapter takes 3" PVC only.
- Install a bird screen at every vent and air termination. Weil-McLain sidewall vent caps include the screen.
If the unit shows an error code, look it up: Weil-McLain Boiler codes
Source: ECO Tec series 3 boiler manual, p. 28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.