Weil-McLain Boiler: Altitude derate for input rate

Updated · by Aurora Star Tech Inc.

Altitude derate for input rate on a Weil-McLain boiler: In the USA, input is derated 4% for each 1000 ft above sea level beyond 2000 ft. In Canada, input is derated 10% for 2000 to 4500 ft. Use the high altitude fan speed settings. Above 4500 ft in Canada, follow provincial authorities. Above 10,000 ft contact Weil-McLain.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: SVF 1500-3000

How to fix altitude derate for input rate: step by step

  1. Check the elevation of the install.
  2. Apply the derate rule for the country.
  3. Use the high altitude rpm column from the blower speed tables.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Weil-McLain Boiler codes

More commissioning tips for boiler

Source: SVF Series 1 boiler manual, p. 88. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.