Viessmann Boiler: Tools needed for service and analysis
Tools needed for service and analysis on a Viessmann boiler: Use only calibrated test equipment. The list covers the electrical, combustion, gas pressure and cleaning tools needed for start-up and service.
Applies to: Vitodens 200-W B2HA 19, 28, 35
How to fix tools needed for service and analysis: step by step
- Use a multimeter for 0 to 230 V AC, 0 to 12 A AC and 0 to 100 mA DC.
- Use a flue gas analyzer that reads % CO2 or O2.
- Use a manometer for gas pressure from 0 to 11 in. w.c. (accurate) and up to 28 in. w.c. A non-electric Magnehelic manometer may also be used.
- Use a stack thermometer from 0 to 500 °F (0 to 260 °C).
- Use a combustion efficiency calculator or suitable tables.
- Use carbon monoxide measuring equipment from 0 to 400 ppm.
- Clean with a plastic hand brush and rags.
- Use an approved leak detection fluid for natural gas and liquid propane, and pipe joint sealant.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 200-W B2HA service instructions, p. 6. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.