Other: Boiler tips (part 35 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Test equipment needed
Viessmann · Vitodens 222-F B2TB 19, 35, 68, 125
Use calibrated equipment only.
- Use a multimeter for 0-230 V AC, 0-12 A AC and 0-100 mA DC.
- Use a flue gas analyzer that measures CO2 or O2.
- Use a manometer for gas pressure from 0 to 11 in. w.c., and up to 28 in. w.c. (a non-electric Magnehelic gauge can also be used).
- Use a stack thermometer rated 0 to 500 °F (0 to 260 °C).
- Use a CO meter rated 0 to 400 ppm.
- Use a Bacharach calculator or suitable tables to work out efficiency.
Test equipment needed for service
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
Bring calibrated instruments only. The manual lists the following for combustion and gas checks.
- Bring a flue gas analyzer that measures % CO2 or O2.
- Bring a multimeter for 0-120 VAC, 0-25 A AC and 0-100 microamps DC.
- Bring a gas pressure gauge that reads 0 to 28 in. w.c. (a non-electric Magnehelic gauge at 0 to 10 psig also works).
- Bring a carbon monoxide meter that reads 0 to 400 ppm.
- Bring a stack thermometer that reads 0°F to 250°F (0°C to 121°C).
- Bring a 1/8 in. NPT male to 1/4 in. barb adaptor and tubing for pressure readings.
- Bring a leak detection fluid approved for natural gas and propane.
Test equipment needed for start-up
Viessmann · Vitodens 100-W WB1B start-up and service
Use calibrated equipment only. Needed: multimeter (0-12A, 120V and resistance); flue gas analyzer for CO2 or O2; manometer for gas pressure 0 to 11 in. w.c. (accurate) and up to 28 in. w.c. (a Magnehelic may be used); stack thermometer 0 to 500°F (0 to 260°C); efficiency calculator or tables; CO meter 0 to 400 ppm. Also leak detection fluid approved for natural gas, pipe joint sealant, a garden hose for bleeding and pressure testing, plastic hand brush and rags.
Therm-control (return temperature)
Viessmann · Heating circuits with therm-control
If the boiler return temperature drops below the set-point read by the therm-control sensor, heating circuit output is reduced. Mixing valves close until the therm-control sensor is satisfied.
- Check the therm-control sensor reading against the set-point when return temperature is low.
- Verify the mixing valves close when the sensor is satisfied.
Thermostat location
Viessmann · Room thermostat installation
Mount the room thermostat on an inside wall away from drafts, hot or cold water pipes, lights, television, sun, or fireplaces.
- Pick an inside wall clear of drafts, pipes, lights and heat sources.
- Follow the thermostat instructions.
Three-phase equipment needs additional power contactors
Viessmann · Vitotronic 300, Model GW2 system types
Three-phase pumps or equipment connected to the system must be switched through additional power contactors, not directly from the control unit.
- Connect any three-phase equipment through separate power contactors.
- Confirm the wiring against the circuit diagram supplied for the system.
Three-phase equipment wiring
Viessmann · All circuit diagrams 5 to 9
Three-phase equipment must be connected through additional power contactors.
- Install additional power contactors for any three-phase equipment in the system.
Time master and DCF receiver behaviour
Viessmann · Multi-controller BUS systems
Only one controller on the BUS can be the time master. When a time master or DCF radio receiver is in the system, the time is blanked on the other controllers. A DCF receiver keeps the time correct. Without DCF, the clock can drift by up to 2 minutes per month.
- Correct the time manually if it drifts, when no DCF receiver is connected.
Time program setup method
Viessmann · Central heating, DHW heating and DHW recirculation pump
Each time program day can have up to 4 time phases, each with its own start and end. Outside the time phases, the system uses reduced temperature.
- From the home screen, select the heating circuit, then time program heating.
- Select the day, then set the start and end points for each time phase.
- Use add to create more phases, then confirm.
- To copy a day's program, select the day, use copy, pick the target days and confirm.
- To change or delete a phase, select the day, select the phase and edit or delete it, then confirm.
Tools and test equipment for service
Viessmann · All VD2 sizes 320 to 1080
Use calibrated test equipment only. Keep the original Viessmann parts; incorrect parts can cause unsafe operation and void the warranty.
- Have flathead and Phillips screwdrivers, pipe wrenches, open-ended wrenches, Allen keys and a flashlight.
- Have pipe sealant and approved leak detection fluid for natural gas and propane.
- Bring the supplied cleaning brush, a hand brush, a vacuum cleaner and rags.
- Bring a flue gas analyzer to measure CO2 or O2, a multimeter (0-120 VAC, 0-12 AAC, 0-20 microamp DC), a smoke test gun, and a CO meter (0-400 ppm).
- Bring oil pump pressure and vacuum gauges if servicing an oil burner.
- Bring a gas pressure gauge (0-7 in. w.c., and up to 28 in. w.c.) or a non-electric Magnehelic gauge.
- Bring an efficiency calculator or tables, and a stack thermometer (0-500 F / 0-260 C).
- Bring a 1/8 in. NPT male to 1/4 in. barb adaptor and tubing for pressure readings.
Tools needed for service and analysis
Viessmann · Vitodens 200-W B2HA 19, 28, 35
Use only calibrated test equipment. The list covers the electrical, combustion, gas pressure and cleaning tools needed for start-up and service.
- Use a multimeter for 0 to 230 V AC, 0 to 12 A AC and 0 to 100 mA DC.
- Use a flue gas analyzer that reads % CO2 or O2.
- Use a manometer for gas pressure from 0 to 11 in. w.c. (accurate) and up to 28 in. w.c. A non-electric Magnehelic manometer may also be used.
- Use a stack thermometer from 0 to 500 °F (0 to 260 °C).
- Use a combustion efficiency calculator or suitable tables.
- Use carbon monoxide measuring equipment from 0 to 400 ppm.
- Clean with a plastic hand brush and rags.
- Use an approved leak detection fluid for natural gas and liquid propane, and pipe joint sealant.
Touchscreen navigation and screensaver
Viessmann · Vitotronic 300 GW6C with HI932 Graphical User Interface
The control has a touchscreen. The screensaver appears after a period with no input, and footer buttons move through the menu.
- If the screensaver is active, tap the screen to return to the default display or home screen.
- Use the footer buttons to return to the home screen, go back one menu level or cancel a setting, call up help text, call up fault or service messages, and scroll.
- From anywhere in the menu, tap the home button to return to the default display.
Transformer and zone valve wiring option
Viessmann · Vitocrossal CU3A Application 2 wiring
If a field-supplied 24 V transformer is not wanted, a multi-zone valve control can be used instead.
Turn off gas to the appliance
Viessmann · Vitodens 200-W B2HA 19, 28, 35
Used before service work or when the appliance will not run.
- Set thermostat or operating control to lowest setting.
- Turn off all electric power to the appliance if service is to be performed.
- Close the main gas shut-off valve.
Two-wrench method for connections
Viessmann · All piping connections
Support the boiler connector while tightening pipe fittings to avoid damaging the boiler's internal piping.
- Use one wrench on the boiler connector and a second on the fitting or pipe.
- Do not use pliers on the gas pipe.
Two-wrench method on boiler connections
Viessmann · Heating water and gas connections
Support the boiler connection while tightening fittings. Without support the boiler internal piping or the pressure gauge can be damaged.
- Use one wrench to hold the boiler connector.
- Use a second wrench to tighten the fitting or pipe.
- Support all piping with hangers, not the boiler.
Unboxing and box contents
Viessmann · Versatronik 200 control
The box holds the manual, outdoor temperature sensor, DHW sensor, common supply/LLH sensor, two CoCo OT communication modules, plug-in terminals and fuses. Check the quantities against the list before you start.
- Check the box contents against the packing list.
- Confirm you have 2 CoCo OT modules for each OpenTherm boiler, or order extra modules.
Underfloor heating and setback savings
Viessmann · Underfloor heating systems
Underfloor heating responds very slowly to short temperature changes. Reduced heating at night or Economy mode during short absences saves little energy on these systems.
Underfloor heating high-limit protection
Viessmann · Vitodens 200-W B2HA 45, 60 underfloor heating
Underfloor loops can overheat concrete slabs if not protected.
- Install an immersion or strap-on aquastat in the low temperature underfloor loop, downstream of the mixing valve.
- Set it to de-energize the pump and/or boiler on high temperature.
Underfloor heating high-temperature protection
Viessmann · Vitocrossal 300 CU3A with underfloor heating
Underfloor loops are damaged by high water temperature, so an extra aquastat is needed to stop the pump and boiler if the loop overheats.
- Install an immersion or strap-on aquastat in the low-temperature underfloor loop, downstream of the mixing valve.
- Set it to de-energize the pump and/or boiler when the loop overheats.
Underfloor heating limit thermostat
Viessmann · Underfloor heating circuits
The electronic maximum limit does not replace the limit thermostat required for underfloor heating. The limit thermostat switches the heating circuit pump off when supply temperature exceeds its preset value. Supply cools slowly, so automatic restart can take several hours.
- Confirm the separate underfloor limit thermostat is installed.
- Warn the user that restart after a trip can take several hours.
Underfloor heating overheating protection
Viessmann · Vitocrossal 200 CI2 399 to 2000
Underfloor loops need an extra immersion or strap-on aquastat in the low temperature loop after the mixing valve. The aquastat de-energizes the pump and/or boiler to stop overheating. High water temperature can damage concrete slabs. System separation is required where non-oxygen diffusion barrier tubing is used, and all secondary-side components must be corrosion resistant.
- Install an immersion or strap-on aquastat in the low temperature underfloor loop, downstream of the mixing valve.
- Wire the aquastat to de-energize the pump and/or boiler on high temperature.
- Separate the system where non-oxygen diffusion barrier tubing is used.
- Use corrosion-resistant materials on the secondary side of the heat exchanger.
Underfloor plastic tubing and oxygen diffusion barrier
Viessmann · Vitorond 200 VD2 hydronic systems
Underfloor plastic tubing without an oxygen diffusion barrier can corrode the system. The warranty does not cover those leaks.
- Use underfloor tubing with an oxygen diffusion barrier, which Viessmann recommends.
- If tubing without a barrier is used, separate it from the boiler with a heat exchanger.
Underfloor plastic tubing without oxygen barrier
Viessmann · Vitorond 200 VD2A hydronic system
Underfloor plastic tubing without an oxygen diffusion barrier can cause corrosion. Such a system must be separated from the boiler with a heat exchanger. The warranty does not cover resulting leaks.
- Separate non-barrier underfloor tubing from the boiler with a heat exchanger.
- Use underfloor tubing with an oxygen diffusion barrier where possible.
Use a 1 in. full port drain if local code requires it
Viessmann · Boiler wash-out and drain
The boiler has a 1 in. wash-out opening that is reduced to a ¾ in. fill/drain faucet. If local codes need a full-port drain, a 1 in. field-supplied tee is installed at the wash-out opening.
- Connect the ¾ in. fill/drain faucet with a 1 in. x ¾ in. reducing coupling.
- If local code requires a full-port drain, fit a 1 in. tee at the wash-out opening.
Use a soap solution for gas leak checks
Viessmann · Vitocrossal 200 CI2
Do not use open flame or matches to check for gas leaks.
- Keep open flame and other ignition sources out of the room.
- Use a soap-and-water solution to check gas connections.
- Never purge a gas line into the combustion chamber.
Use only original Viessmann parts
Viessmann · Vitorond 200 VD2A boilers
Replacement parts must be original Viessmann components. Wrong parts can make the boiler operate unsafely and void the warranty. Order replacement parts through a Viessmann distributor and use the Parts List in the manual.
- Check the Parts List before ordering any replacement.
- Order parts from a Viessmann distributor.
- Do not fit non-Viessmann parts.
Use only original Viessmann replacement parts
Viessmann · Vitorond 200 VD2A
Installing incorrect replacement parts can cause hazardous operation and will void the warranty.
- Order replacement components from your Viessmann distributor.
- Use only original Viessmann components when replacing defective parts.
- Use the Parts List (starting page 17) to identify the correct component.
Use only Viessmann replacement parts
Viessmann · All Vitocrossal 200 CM2 units
Non-approved parts can cause hazardous operation and void the warranty. The full parts list starts on page 50.
- Order replacement components from a Viessmann distributor.
- Use only original Viessmann recommended components when replacing defective parts.
- Do not repair safety-function components; replace them.
Use the 4th DHW time phase for higher DHW temperature
Viessmann · Vitocrossal 300 CA3B with Vitotronic 300 GW6C
The heating contractor can enable a second, higher DHW set temperature. It runs during time phase 4. The 2nd and 3rd time phases must have start and stop times set.
- Ask the heating contractor to enable the second DHW set temperature.
- Set start and stop times for time phase 4.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.