Viessmann Boiler: Simplified coaxial vent leak test
Simplified coaxial vent leak test on a Viessmann boiler: Check the air intake coaxial gap for leaks during start-up by measuring the combustion air. The vent is acceptable if CO2 is 0.2% or lower, or O2 is 20.6% or higher. If the readings are worse, check the venting system thoroughly.
Applies to: Vitodens 200-W B2HA, all sizes
How to fix simplified coaxial vent leak test: step by step
- Use the two measurement ports on the vent pipe adaptor (one for air intake, one for flue gas).
- Measure CO2 in the combustion air in the coaxial gap of the air intake pipe.
- If CO2 is above 0.2% or O2 is below 20.6%, check the whole venting system for leaks.
If the unit shows an error code, look it up: Viessmann Boiler codes
More commissioning tips for boiler
Source: Vitodens 200-W B2HA 112, 150, 399, 530 Service Instructions, p. 24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.