Viessmann Boiler: Replace the flow limiter
Replace the flow limiter on a Viessmann boiler: Water can leak when the flow limiter is replaced. Shut off the cold water supply and drain the DHW line and the plate type heat exchanger (DHW side) first.
Applies to: CombiPLUS flow limiter
Common causes of replace the flow limiter
- Faulty flow limiter
How to fix replace the flow limiter: step by step
- Shut off the cold water supply.
- Drain the DHW line and the plate type heat exchanger (DHW side).
- Drain the boiler and CombiPLUS.
- Remove the screws from the cover and remove the cover.
- Undo screws A.
- Remove the cap B.
- Remove the faulty flow limiter C.
- Select a new flow limiter that matches the boiler size on the rating plate. The size table is on page 26 of the installation instructions, not in this extract.
- Insert the new flow limiter C.
- Fit the new cap B provided.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitodens 100-W, WB1B CombiPlus Installation & Service, p. 82. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.