Viessmann Boiler: Reinstalling the burner after service
Reinstalling the burner after service on a Viessmann boiler: Burner refit sequence with torque values and gas connection checks.
Applies to: Vitodens 100-W WB1B
How to fix reinstalling the burner after service: step by step
- Replace the electrical cables from the fan motor, mount the burner, and diagonally tighten the 4 Torx T-30 screws to 4 Nm (35 lb.in.).
- Insert a new gasket and tighten the gas connection pipe fitting to 15 Nm (132 lb.in.).
- Plug the Venturi extension into the fan.
- Replace the electrical cables from the gas valve and the electrode block.
- Open the gas shutoff valve and switch on the power supply.
- Check the gas connection for tightness.
- Install the front panel (see page 52).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitodens 100-W WB1B installation and service instructions, p. 72. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.